Advanced packaging
Thermal Management in 2.5D and 3D Packages: Why Stacking Makes Heat Harder, and What Liquid Cooling Changes
Quick answer
A package moves heat from a die to the outside world through a chain of layers in series: the silicon itself, a thermal interface material (TIM), a lid or heat spreader, a second TIM, and then a heat sink or a liquid-cooled cold plate [P1][P7]. Engineers describe each link by a thermal resistance in °C/W, and the junction temperature is the ambient temperature plus the sum of those resistances times the power [P1]; with a cold plate, this page takes the coolant temperature as that reference [interpretation]. Stacking dies in three dimensions does two things to that chain: heat generated inside a stack has to cross the interfaces between the dies before it leaves, and a hot neighbor adds thermal coupling, so an HBM stack next to a processor is heated by power it did not dissipate [P3][P5]. A review of hybrid-bonded HBM reports that internal heat buildup becomes more severe beyond 12 layers, and that the hybrid-bonding studies it synthesizes report cuts in junction-to-junction thermal resistance of between 22.8% and 47%, in studies of different stack heights and methods [P3]. At the system end, the response is liquid cooling at the package: single-phase cold plates mounted on the processor, now covered by an open test specification and described by one vendor as the cooling of its rack-scale systems [P6][S1][S2].
Why stacking makes heat harder
Heat flows in series. In a conventional single-die package the path is short: die, TIM, integrated heat spreader (IHS), TIM, heat sink [P7]. Intel's design guide lists the IHS and the TIM among its defined terms [P7]. Each layer has a thermal resistance, and resistances in series add, so the junction temperature for a given power is set by the sum [P1]. For conduction through a slab, the resistance is the thickness divided by the product of conductivity and area, R = L/(kA), so doubling a layer's thickness or halving its conductivity doubles its resistance [definition]. In a series path, every extra interface is an extra term in the sum.
A stack puts interfaces in the path. When memory dies are stacked, the review cited here says, heat generated within the dies has to travel through interfaces such as TSVs and underfill layers before it reaches the dies below or above [P3]. Its abstract says the three-dimensional stack "traps heat and amplifies thermo mechanical stress", and it reports that internal heat buildup becomes more severe as the stack grows beyond 12 layers [P3]. The review extends its own quantitative analysis to stacks of 16 layers and more [P3].
Neighbors matter. The thermal chapter of the Heterogeneous Integration Roadmap describes "closely packed chiplets and strong cross-die thermal coupling", warns that "localized hotspot and cross-die thermal coupling can have a severely negative impact" on a 3D-IC, and says that hotspots "need to be studied in a fast end-to-end manner" [P5]. The same chapter discusses HBM in terms of the thermal resistance of the stack and thermal coupling from adjacent logic, and says that testing a large 3D-IC that includes CPUs or GPUs is a major challenge because of "multiple localized thermal hotspots" [P5]. In this page's interpretation, this is why a memory stack that dissipates modest power can still be the limiting component of a package: its temperature depends on the processor next to it as well as on its own dissipation [interpretation].
The words on a datasheet
Package thermal data use a small vocabulary; the application note cited here explains it with reference to the JEDEC JESD51 series [P1]. θJA "is the thermal resistance from junction to ambient, measured as °C/W", specified under natural convection on a standard test board [P1]. θJC "is the thermal resistance from junction to case", measured with the case held on an infinite heat sink, and is always smaller than θJA [P1]. The Ψ (psi) values are thermal-characterization parameters rather than resistances: ΨJT relates the junction to the temperature at the top center of the package, and ΨJB to a point on the board within 1 mm of the package edge, for conditions in which heat leaves by more than one path [P1]. The formulas have the same form, T_J = T_A + θJA × P and T_J = T_T + ΨJT × P, and the note describes ΨJT as useful for estimating the junction temperature [P1]. The application note is blunt about the standard numbers: the JEDEC configurations "do not represent typical real-world systems" and "are most useful for comparing the thermal figures of merit among package variations" [P1]. In this page's reading, θJA is first a number for comparing packages, and a system's junction temperature has to be estimated for its own board and airflow [interpretation].
Processor vendors add one more layer of language for lidded packages. An Intel design guide for server processors defines where the case temperature T_CASE is measured and defines Ψ_CA, the case-to-ambient characterization parameter, as (T_CASE − T_LA) / TDP, where TDP is the thermal design power and T_LA is defined as "Average ambient temperature entering the processor heat sink fin section (°C)" [P7]. Ψ_CA is then split into a case-to-sink term and a sink-to-ambient term, Ψ_CA = Ψ_CS + Ψ_SA, and the guide adds: "Heat source should always be specified for Ψ measurements" [P7]. The guide also defines a thermal profile for the case temperature and states that "TDP is not the maximum power that the processor can dissipate" [P7].
In this page's interpretation, one thing carries over from this single-die vocabulary to 2.5D and 3D packages and two do not carry over unchanged [interpretation]. The series-sum picture carries over. The Ψ decomposition is defined against the air entering a heat sink, so applying it to a cold plate and its coolant means redefining the reference temperature and the measurement points, which the guide cited here does not do [P7]. And the "one junction temperature" picture does not carry over: a package with a processor and several memory stacks has many junctions, each with its own limit, and the hottest is not necessarily the one dissipating the most.
Inside the stack: bonds, underfill and copper
The layers between stacked dies are where 3D packaging adds resistance, and they are also where it can be removed. The Chungbuk review collects the published comparisons, each from its own test structure or simulation [P3]. Interface resistance for a copper hybrid bond was reported at 1.2 mm²·K/W against 4.2 mm²·K/W for microbumps at a 40 µm pitch, and 8–19 mm²·K/W for microbumps in another study (figures as cited in the review) [P3]. Halving the bump pitch from 100 µm to 50 µm lowered the maximum chip temperature by 12 °C in one study of a structure without TSVs; replacing thermo-compression non-conductive film with mass-reflow molded underfill lowered the maximum junction temperature by 14 °C in another; and direct bond interconnect reduced the junction temperature by approximately 26% in a study of an 8-die stack [P3]. In its abstract the review says the hybrid-bonding studies it synthesizes can "cut junction-to-junction thermal resistance by between 22.8% and 47%" and "raise vertical thermal conductivity by up to three times"; the two ends of the range come from an 8-high analysis and a 16-high simulation [P3]. It also names "at least 20% Cu coverage" as a design threshold that balances heat flow, interfacial stress and reliability [P3]. Copper's conductivity, about 390 W/m·K, is why the copper fraction of the interface matters; in the study behind the 20% figure, on a 64-core RISC-V system-on-chip design, the maximum temperature stabilized once the metal density exceeded 20% and further increases brought only marginal reductions, and the review adds that high-density copper pads can raise thermal stress at the interface [P3].
Underfill and TIM chemistry move the same numbers from the other side. The review lists filled-epoxy and boron-nitride composites with thermal conductivities from about 0.85 to 10.18 W/m·K depending on filler and loading [P3]. Among external measures, one study the review cites found that a through mold plate, positioned between the GPU and the HBM, "can reduce the HBM junction temperature by approximately 10.3 °C" [P3]. But the review's conclusion for external measures is the sentence to remember: "external cooling alone is insufficient to fully control internal thermal resistance" [P3]. In this page's reading, a better cold plate lowers the temperature that the whole stack sits on, while the resistance between the dies is set inside the stack [interpretation].
Cross-reference: how hybrid bonds and microbumps are made is in Hybrid Bonding vs Microbumps; through-silicon vias are in TSV vs TGV.
Liquid cooling arrives at the package
Why. The series sum has a last term, from the case to the ambient [P1]. The roadmap chapter's section on liquid cooling reports one comparison in which water-cooled cold plates "offered 41% higher clock rates compared to air cooled heat sink", and a separate study of microfluidic cooling etched directly into the back of a processor die that reported up to 44.4% lower thermal resistance than a conventional cold plate (single studies, as the chapter reports them) [P5]. The same chapter treats hotspots and cross-die coupling as properties of the 3D-IC itself, which is why, in this page's reading, cooling has to be designed together with the stack [P5][interpretation].
What a cold plate is, in a test specification's words. The Open Compute Project's test specification for single-phase direct-to-chip cold plates, effective September 2026, defines the device as a "liquid-cooled heat exchanger" that mounts on the processor with a TIM and runs "a single-phase closed liquid loop" [P6]. Thermal resistance is calculated as R = (Ts − Tl)/P, from the temperature at the base of the cold plate (Ts), the incoming fluid temperature (Tl) and the applied power (P), with the fluid "typically 45°C ± 2°C", and the test "is repeated at multiple flow rates to generate a performance curve" [P6]. Pressure drop is measured separately, at "at least six flow rates from 25% to 150% of rated flow" [P6]. The specification also sets out other validation tests for the cold plate: flow at increasing rates "up to <1.5 m/s to ensure no erosion or leaks"; leak detection with pressurized hydrogen or helium, with an example criterion of less than 0.6 SCCM; a burst-pressure test with an example minimum above 20 bar; operational temperature cycling between 10 °C and 65 °C with 72-hour dwells; non-operational cycling for shipping between −40 °C and +70 °C; and a cleanliness requirement of particulate under 50 µm [P6]. It covers design and prototype qualification; production and factory acceptance testing are outside its scope [P6]. None of this is exotic; it is the vocabulary a package engineer now needs alongside θJC.
Why warm water is the point. A cold plate fed with coolant at 45 °C sounds like a poor cooler, and the temperature is deliberate. NVIDIA's account is that coolant enters at up to 45 degrees Celsius and leaves at roughly 55, and that in favorable climates its 45-degree architecture "can enable chiller-less operation with dry coolers"; the same post keeps chillers in the picture for other locations and conditions [S2]. In this page's interpretation, the package-level consequence is a warm reference temperature: the temperature rise across die, TIM1, lid, TIM2 and cold plate has to fit between the coolant temperature and the junction limit, which puts pressure on each interface in the chain [interpretation].
Status as of 2026-11
The statements below are dated and attributed to their sources.
- Rack-scale liquid cooling, as one vendor describes its systems. NVIDIA describes the GB200 NVL72 and the GB300 NVL72 as rack-scale, liquid-cooled systems and cites a full-rack power density of 120 kW (vendor statements, April 2025) [S1]. In October 2026 NVIDIA and Oracle described Oracle's existing infrastructure as "including NVIDIA GB200 and GB300 NVL72 systems" [S7]. Status: announced for the cooling description, 2025-04; deployment as quoted above, 2026-10. The sources used do not state shipment or production volumes.
- A 45 °C inlet and fully liquid-cooled racks for the following generation. NVIDIA states that coolant enters at up to 45 degrees Celsius and exits at roughly 55, and describes the Rubin generation as "the world's first to achieve 100% liquid cooling" (vendor statements, June 2026) [S2]. NVIDIA announced on 31 May 2026 that "the NVIDIA Vera Rubin platform is ramping into full production", and wrote on 30 September 2026 that CoreWeave "received its first Vera Rubin NVL72 production racks" earlier that month [S5][S6]. Status: announced for the cooling claims, 2026-06; production status as quoted above, 2026-05 and 2026-09. The posts cited as [S1] and [S2] are about 14 months apart and their figures are not combined on this page.
- A cold-plate test specification is published. The OCP single-phase direct-to-chip cold plate test specification is at version 1.0.0, effective 2026-09-03 [P6]. Status: published standard, 2026-09.
- Stacking memory on logic is a research simulation, not a product. As reported in the trade press from imec's IEDM 2025 presentation, imec modeled 12-die hybrid-bonded HBM stacks placed directly on GPUs, and the report gives a peak GPU temperature of 141.7 °C against 69.1 °C for the 2.5D arrangement, brought down to 70.8 °C by combining stack merging, silicon thermal optimization, double-sided cooling and GPU frequency scaling (simulation results as reported) [S3]. Status: research simulation, 2025-12.
Common mistakes
Reading θJA as a prediction. It is measured on a JEDEC test board under natural convection, and the application note that defines it says the configurations "do not represent typical real-world systems" [P1].
Treating TDP as a maximum. In the vendor's own words, "TDP is not the maximum power that the processor can dissipate" [P7].
Expecting a better cold plate to fix a stack. The review's finding is that "external cooling alone is insufficient to fully control internal thermal resistance", and it points to bonding optimization within the structure instead [P3].
Quoting one junction temperature for a multi-die package. A processor beside memory stacks has many junctions with different limits, and the coupling between them is part of the design [P5][interpretation].
Combining vendor figures from different posts. A water-efficiency figure and a 45 °C inlet figure come from two posts about 14 months apart that describe different generations; this page keeps them apart [S1][S2].
Engineering interpretation, and what is uncertain
The following is interpretation drawn only from the sources above.
Thermal management has moved from the end of the design to the middle of it. In this page's reading, in a 3D package the heat path runs through the stack, so the bond pitch, the copper fraction at each interface and the choice of underfill are thermal choices as well as electrical and mechanical ones [P3]. The 20% metal-density figure and the 12-layer observation are results from particular studies, with the diminishing returns and stress penalties the review attaches to them, and not general design limits [P3].
The test specification matters as well as the cold plates. It is an openly published specification with stated test conditions, under which a cold plate's thermal resistance is characterized against a fluid temperature and a range of flow rates, for design and prototype qualification [P6]. In this page's reading, that gives a package designer a published way to compare cold plates; the 45 °C in the specification is a typical test temperature and the 45 °C in the vendor's account is an inlet capability, and the two should not be read as the same number [P6][S2].
Uncertain: the figures quoted here are from the studies a review collected, each with its own geometry, and the review itself notes that "differences in experimental conditions and the lack of long-term reliability data hinder direct comparisons across studies" [P3]; the imec result is a simulation as reported in the trade press, and imec's own release was not read in full for this page [S3]; the Intel design guide used here is the 2013 edition for an earlier processor family, and later editions were not read [P7]; vendor statements about cooling and production are vendor statements, dated [S1][S2][S5][S6][S7]; the Heterogeneous Integration Roadmap chapter is published for technology assessment and its figures and tables are not reproduced here [P5]. Nothing on this page describes any company's internal thermal test practice.
Further reading and sources
On this site: HBM Explained for what is being stacked; CoWoS Explained for the interposer the dies sit on; Hybrid Bonding vs Microbumps for the bond layers compared above; Backside Power Delivery Explained for the self-heating concern in thinned silicon; TSV vs TGV for the vertical vias; Chiplets Explained for why dies are placed side by side.
Sources (grade A unless noted):
- Analog Devices (originally Maxim Integrated App Note 4083), "Thermal Characterization of IC Packages," 30 July 2007 — definitions of θJA, θJC, θJB, ΨJT, ΨJB and the JESD51 series [P1].
- S.-H. Lee, S.-J. Kim, J.-S. Lee, S.-H. Rhi, "Thermal Issues Related to Hybrid Bonding of 3D-Stacked High Bandwidth Memory: A Comprehensive Review," Electronics 14(13), 2682, 2 July 2025, doi:10.3390/electronics14132682 (B; open access, CC BY; third-party figures cited through this review are marked as such) [P3].
- IEEE EPS, Heterogeneous Integration Roadmap 2023 Edition, Chapter 20: Thermal, March 2023 (publicly posted; "intended for technology assessment only"; figures and tables not reproduced) [P5].
- Open Compute Project, "Single-Phase Direct-to-Chip Cold Plate Test Specification," V1.0.0, effective 3 September 2026 [P6].
- Intel, "Intel Xeon Processor E5-1600/2600/4600 v1 and v2 Product Families Thermal / Mechanical Design Guide," 326512-003, September 2013 [P7].
- NVIDIA, M. Hamilton, "Chill Factor: NVIDIA Blackwell Platform Boosts Water Efficiency by Over 300x," NVIDIA Blog, 22 April 2025 (vendor statement) [S1].
- NVIDIA, J. Parker, "Hotter Than a Hot Tub: The 45°C Breakthrough to Cool AI's Biggest Machines," NVIDIA Blog, 21 June 2026 (vendor statement) [S2].
- eeNews Europe, "Imec tackles thermal limits in 3D HBM-on-GPU architectures," 10 December 2025, reporting imec's IEDM 2025 presentation (B) [S3].
- NVIDIA, press release "NVIDIA Vera Rubin Ramps Into Full Production to Power Agentic AI Factories Worldwide," 31 May 2026 (vendor statement) [S5].
- NVIDIA, S. Pitts, "From Training to Production, NVIDIA and CoreWeave Close the Loop on Agentic AI," NVIDIA Blog, 30 September 2026 (vendor statement) [S6].
- NVIDIA, press release "NVIDIA and Oracle Expand NVIDIA Vera Rubin to Multi-Gigawatt Scale and Bring NVIDIA Vera CPU to Oracle Cloud Infrastructure," 27 October 2026 (vendor statement) [S7].